Frequently Asked Questions
    THIS ONE FIRST
      Q. ‘How do I program unit?’
      A. Take a look at the .pdf  instruction manual first. It will help to familiarise yourself with the  layout and general operation so guidance will be easier should you still need  to call.
    Q. ‘Pola HP11—I have power on unit, it has switched on but there isn’t power  getting to boiler/pump/heater?’
      A. Check that there is power  connected to terminal 4 (‘Common’ supply terminal of output relay) If there  isn’t power going into common, you won’t get power out of the switched live.
    Q.  ‘POLA Can I extend the cable length?’
      A. Yes, use 2 core copper wire  of about 0.75mm squared cross sectional area. You should not need to  recalibrate. Avoid cable runs in same conduit/truncking as mains cable or you  may effect sensor reading. As a rule of thumb, try to keep them at least 10/12”  appart.
    Q. ‘Temperature reading is oscillating rapidly up and down’
      A. The sensor cable is probably  being effected by being to close to a mains cable. Avoid cable runs in same  conduit/truncking as mains cable or you may effect sensor reading. As a rule of  thumb, try to keep them at least 10/12” appart.
    Q. ‘Temperature doesn’t read what is expected’
      A. Make sure sensor tip is  precisely where you want temperature measured. Remember ‘temperature gradients’  (Temperature will be hottest at heater surface and coldest at extreme locations  and so depending on where the sensor tip is placed between the 2 the reading  will vary) Same applies for vertical applications—heat rises.